Search Results (2336 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2025-40760 1 Siemens 1 Altair Grid Engine 2026-04-15 5.5 Medium
A vulnerability has been identified in Altair Grid Engine (All versions < V2026.0.0). Affected products do not properly handle error messages and discloses sensitive password hash information when processing user authentication requests. This could allow a local attacker to extract password hashes for privileged accounts, which can then be subjected to offline brute-force attacks.
CVE-2025-40591 1 Siemens 11 Ruggedcom Rox Mx5000, Ruggedcom Rox Mx5000re, Ruggedcom Rox Rx1400 and 8 more 2026-04-15 7.7 High
A vulnerability has been identified in RUGGEDCOM ROX MX5000 (All versions < V2.16.5), RUGGEDCOM ROX MX5000RE (All versions < V2.16.5), RUGGEDCOM ROX RX1400 (All versions < V2.16.5), RUGGEDCOM ROX RX1500 (All versions < V2.16.5), RUGGEDCOM ROX RX1501 (All versions < V2.16.5), RUGGEDCOM ROX RX1510 (All versions < V2.16.5), RUGGEDCOM ROX RX1511 (All versions < V2.16.5), RUGGEDCOM ROX RX1512 (All versions < V2.16.5), RUGGEDCOM ROX RX1524 (All versions < V2.16.5), RUGGEDCOM ROX RX1536 (All versions < V2.16.5), RUGGEDCOM ROX RX5000 (All versions < V2.16.5). The 'Log Viewers' tool in the web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated remote attacker to execute the 'tail' command with root privileges and disclose contents of all files in the filesystem.
CVE-2024-31484 1 Siemens 2 Cpc80 Central Processing\/communication, Cpci85 Central Processing\/communication 2026-04-15 7.8 High
A vulnerability has been identified in CPC80 Central Processing/Communication (All versions < V16.41), CPCI85 Central Processing/Communication (All versions < V5.30), CPCX26 Central Processing/Communication (All versions < V06.02), ETA4 Ethernet Interface IEC60870-5-104 (All versions < V10.46), ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2 (All versions < V03.27), PCCX26 Ax 1703 PE, Contr, Communication Element (All versions < V06.05). The affected devices contain an improper null termination vulnerability while parsing a specific HTTP header. This could allow an attacker to execute code in the context of the current process or lead to denial of service condition.
CVE-2011-20002 1 Siemens 3 Simatic, Simatic S7-1200, Simatic S7-1200 Cpu 2026-04-15 7.4 High
A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured.
CVE-2022-45147 1 Siemens 2 Simatic Pcs Neo, Simatic Step 7 2026-04-15 7.8 High
A vulnerability has been identified in SIMATIC PCS neo V4.0 (All versions), SIMATIC STEP 7 V16 (All versions), SIMATIC STEP 7 V17 (All versions), SIMATIC STEP 7 V18 (All versions < V18 Update 2). Affected applications do not properly restrict the .NET BinaryFormatter when deserializing user-controllable input. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application. This is the same issue that exists for .NET BinaryFormatter https://docs.microsoft.com/en-us/visualstudio/code-quality/ca2300.
CVE-2025-40769 1 Siemens 1 Sinec Traffic Analyzer 2026-04-15 7.4 High
A vulnerability has been identified in SINEC Traffic Analyzer (6GK8822-1BG01-0BA0) (All versions < V3.0). The affected application uses a Content Security Policy that allows unsafe script execution methods. This could allow an attacker to execute unauthorized scripts, potentially leading to cross-site scripting attacks.
CVE-2011-20001 1 Siemens 3 Simatic, Simatic S7-1200, Simatic S7-1200 Cpu 2026-04-15 7.5 High
A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.3), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.3). The web server interface of affected devices improperly processes incoming malformed HTTP traffic at high rate. This could allow an unauthenticated remote attacker to force the device entering the stop/defect state, thus creating a denial of service condition.
CVE-2025-40570 1 Siemens 1 Siprotec 5 2026-04-15 2.4 Low
A vulnerability has been identified in SIPROTEC 5 6MD84 (CP300) (All versions < V10.0), SIPROTEC 5 6MD85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MD86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MD89 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MU85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7KE85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SA82 (CP150) (All versions < V10.0), SIPROTEC 5 7SA86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SA87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SD82 (CP150) (All versions < V10.0), SIPROTEC 5 7SD86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SD87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SJ81 (CP150) (All versions < V10.0), SIPROTEC 5 7SJ82 (CP150) (All versions < V10.0), SIPROTEC 5 7SJ85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SJ86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SK82 (CP150) (All versions < V10.0), SIPROTEC 5 7SK85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SL82 (CP150) (All versions < V10.0), SIPROTEC 5 7SL86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SL87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SS85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7ST85 (CP300) (All versions < V10.0), SIPROTEC 5 7ST86 (CP300) (All versions < V10.0), SIPROTEC 5 7SX82 (CP150) (All versions < V10.0), SIPROTEC 5 7SX85 (CP300) (All versions < V10.0), SIPROTEC 5 7SY82 (CP150) (All versions < V10.0), SIPROTEC 5 7UM85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT82 (CP150) (All versions < V10.0), SIPROTEC 5 7UT85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VE85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VK87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VU85 (CP300) (All versions < V10.0), SIPROTEC 5 Compact 7SX800 (CP050) (All versions < V10.0). Affected devices do not properly limit the bandwidth for incoming network packets over their local USB port. This could allow an attacker with physical access to send specially crafted packets with high bandwidth to the affected devices thus forcing them to exhaust their memory and stop responding to any network traffic via the local USB port. Affected devices reset themselves automatically after a successful attack. The protection function is not affected of this vulnerability.
CVE-2024-30321 1 Siemens 3 Simatic Pcs 7, Simatic Wincc, Simatic Wincc Runtime Professional 2026-04-15 5.9 Medium
A vulnerability has been identified in SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 5), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 23), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 17), SIMATIC WinCC V8.0 (All versions < V8.0 Update 5). The affected products do not properly handle certain requests to their web application, which may lead to the leak of privileged information. This could allow an unauthenticated remote attacker to retrieve information such as users and passwords.
CVE-2025-32469 1 Siemens 11 Ruggedcom Rox Mx5000, Ruggedcom Rox Mx5000re, Ruggedcom Rox Rx1400 and 8 more 2026-04-15 9.9 Critical
A vulnerability has been identified in RUGGEDCOM ROX MX5000 (All versions < V2.16.5), RUGGEDCOM ROX MX5000RE (All versions < V2.16.5), RUGGEDCOM ROX RX1400 (All versions < V2.16.5), RUGGEDCOM ROX RX1500 (All versions < V2.16.5), RUGGEDCOM ROX RX1501 (All versions < V2.16.5), RUGGEDCOM ROX RX1510 (All versions < V2.16.5), RUGGEDCOM ROX RX1511 (All versions < V2.16.5), RUGGEDCOM ROX RX1512 (All versions < V2.16.5), RUGGEDCOM ROX RX1524 (All versions < V2.16.5), RUGGEDCOM ROX RX1536 (All versions < V2.16.5), RUGGEDCOM ROX RX5000 (All versions < V2.16.5). The 'ping' tool in the web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated remote attacker to execute arbitrary code with root privileges.
CVE-2024-39888 1 Siemens 1 Mendix Encryption 2026-04-15 7.5 High
A vulnerability has been identified in Mendix Encryption (All versions >= V10.0.0 < V10.0.2). Affected versions of the module define a specific hard-coded default value for the EncryptionKey constant, which is used in projects where no individual EncryptionKey was specified. This could allow to an attacker to decrypt any encrypted project data, as the default encryption key can be considered compromised.
CVE-2020-28398 1 Siemens 11 Ruggedcom Rox Mx5000, Ruggedcom Rox Mx5000re, Ruggedcom Rox Rx1400 and 8 more 2026-04-15 8.8 High
A vulnerability has been identified in RUGGEDCOM ROX MX5000 (All versions < V2.16.0), RUGGEDCOM ROX MX5000RE (All versions < V2.16.0), RUGGEDCOM ROX RX1400 (All versions < V2.16.0), RUGGEDCOM ROX RX1500 (All versions < V2.16.0), RUGGEDCOM ROX RX1501 (All versions < V2.16.0), RUGGEDCOM ROX RX1510 (All versions < V2.16.0), RUGGEDCOM ROX RX1511 (All versions < V2.16.0), RUGGEDCOM ROX RX1512 (All versions < V2.16.0), RUGGEDCOM ROX RX1524 (All versions < V2.16.0), RUGGEDCOM ROX RX1536 (All versions < V2.16.0), RUGGEDCOM ROX RX5000 (All versions < V2.16.0). The CLI feature in the web interface of affected devices is vulnerable to cross-site request forgery (CSRF). This could allow an attacker to read or modify the device configuration by tricking an authenticated legitimate user into accessing a malicious link.
CVE-2024-39675 1 Siemens 24 Ruggedcom Ros Rmc30, Ruggedcom Ros Rmc30nc, Ruggedcom Ros Rp110 and 21 more 2026-04-15 8.8 High
A vulnerability has been identified in RUGGEDCOM RMC30 (All versions < V4.3.10), RUGGEDCOM RMC30NC (All versions < V4.3.10), RUGGEDCOM RP110 (All versions < V4.3.10), RUGGEDCOM RP110NC (All versions < V4.3.10), RUGGEDCOM RS400 (All versions < V4.3.10), RUGGEDCOM RS400NC (All versions < V4.3.10), RUGGEDCOM RS401 (All versions < V4.3.10), RUGGEDCOM RS401NC (All versions < V4.3.10), RUGGEDCOM RS416 (All versions < V4.3.10), RUGGEDCOM RS416NC (All versions < V4.3.10), RUGGEDCOM RS416NCv2 V4.X (All versions < V4.3.10), RUGGEDCOM RS416NCv2 V5.X (All versions < V5.9.0), RUGGEDCOM RS416P (All versions < V4.3.10), RUGGEDCOM RS416PNC (All versions < V4.3.10), RUGGEDCOM RS416PNCv2 V4.X (All versions < V4.3.10), RUGGEDCOM RS416PNCv2 V5.X (All versions < V5.9.0), RUGGEDCOM RS416Pv2 V4.X (All versions < V4.3.10), RUGGEDCOM RS416Pv2 V5.X (All versions < V5.9.0), RUGGEDCOM RS416v2 V4.X (All versions < V4.3.10), RUGGEDCOM RS416v2 V5.X (All versions < V5.9.0), RUGGEDCOM RS910 (All versions < V4.3.10), RUGGEDCOM RS910L (All versions), RUGGEDCOM RS910LNC (All versions), RUGGEDCOM RS910NC (All versions < V4.3.10), RUGGEDCOM RS910W (All versions < V4.3.10), RUGGEDCOM RS920L (All versions), RUGGEDCOM RS920LNC (All versions), RUGGEDCOM RS920W (All versions). In some configurations the affected products wrongly enable the Modbus service in non-managed VLANS. Only serial devices are affected by this vulnerability.
CVE-2024-22041 1 Siemens 13 Cerberus Pro En Engineering Tool, Cerberus Pro En Fire Panel Fc72x, Cerberus Pro En X200 Cloud Distribution and 10 more 2026-04-15 7.5 High
A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems improperly handles memory buffers when parsing X.509 certificates. This could allow an unauthenticated remote attacker to crash the network service.
CVE-2024-32008 1 Siemens 1 Spectrum Power 4 2026-04-15 7.8 High
A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP12 Update 2). The affected application is vulnerable to a local privilege escalation due to an exposed debug interface on the localhost. This allows any local user to gain code execution as administrative application user.
CVE-2023-50821 1 Siemens 3 Simatic Pcs 7, Simatic Wincc, Simatic Wincc Runtime Professional 2026-04-15 6.2 Medium
A vulnerability has been identified in SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC04), SIMATIC WinCC Runtime Professional V17 (All versions < V17 Update 8), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 4), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 1), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 16), SIMATIC WinCC V8.0 (All versions < V8.0 Update 5). The affected products do not properly validate the input provided in the login dialog box. An attacker could leverage this vulnerability to cause a persistent denial of service condition.
CVE-2024-32010 1 Siemens 1 Spectrum Power 4 2026-04-15 7.8 High
A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP12 Update 2). The affected application is vulnerable to extraction of database credentials via a world-readable credential file. This allows an attacker to connect to the database as privileged application user and to run system commands via the database.
CVE-2024-30207 1 Siemens 1 Simatic Rtls Locating Manager 2026-04-15 10 Critical
A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). The affected systems use symmetric cryptography with a hard-coded key to protect the communication between client and server. This could allow an unauthenticated remote attacker to compromise confidentiality and integrity of the communication and, subsequently, availability of the system. A successful exploit requires the attacker to gain knowledge of the hard-coded key and to be able to intercept the communication between client and server on the network.
CVE-2025-33023 1 Siemens 11 Ruggedcom Rox Mx5000, Ruggedcom Rox Mx5000re, Ruggedcom Rox Rx1400 and 8 more 2026-04-15 4.1 Medium
A vulnerability has been identified in RUGGEDCOM ROX MX5000 (All versions), RUGGEDCOM ROX MX5000RE (All versions), RUGGEDCOM ROX RX1400 (All versions), RUGGEDCOM ROX RX1500 (All versions), RUGGEDCOM ROX RX1501 (All versions), RUGGEDCOM ROX RX1510 (All versions), RUGGEDCOM ROX RX1511 (All versions), RUGGEDCOM ROX RX1512 (All versions), RUGGEDCOM ROX RX1524 (All versions), RUGGEDCOM ROX RX1536 (All versions), RUGGEDCOM ROX RX5000 (All versions). The affected devices do not properly enforce the restriction of files that can be uploaded from the web interface. This could allow an authenticated remote attacker with high privileges in the web interface to upload arbitrary files.
CVE-2025-40761 1 Siemens 11 Ruggedcom Rox Mx5000, Ruggedcom Rox Mx5000re, Ruggedcom Rox Rx1400 and 8 more 2026-04-15 7.6 High
A vulnerability has been identified in RUGGEDCOM ROX MX5000 (All versions), RUGGEDCOM ROX MX5000RE (All versions), RUGGEDCOM ROX RX1400 (All versions), RUGGEDCOM ROX RX1500 (All versions), RUGGEDCOM ROX RX1501 (All versions), RUGGEDCOM ROX RX1510 (All versions), RUGGEDCOM ROX RX1511 (All versions), RUGGEDCOM ROX RX1512 (All versions), RUGGEDCOM ROX RX1524 (All versions), RUGGEDCOM ROX RX1536 (All versions), RUGGEDCOM ROX RX5000 (All versions). Affected devices do not properly limit access through its Built-In-Self-Test (BIST) mode. This could allow an attacker with physical access to the serial interface to bypass authentication and get access to a root shell on the device.