Search Results (424 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2014-2256 1 Siemens 6 Simatic S7 Cpu-1211c, Simatic S7 Cpu 1200 Firmware, Simatic S7 Cpu 1212c and 3 more 2025-04-12 N/A
Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted ISO-TSAP packets, a different vulnerability than CVE-2014-2257.
CVE-2016-4954 5 Ntp, Opensuse, Oracle and 2 more 15 Ntp, Leap, Opensuse and 12 more 2025-04-12 7.5 High
The process_packet function in ntp_proto.c in ntpd in NTP 4.x before 4.2.8p8 allows remote attackers to cause a denial of service (peer-variable modification) by sending spoofed packets from many source IP addresses in a certain scenario, as demonstrated by triggering an incorrect leap indication.
CVE-2014-2908 1 Siemens 6 Simatic S7 Cpu-1211c, Simatic S7 Cpu 1200 Firmware, Simatic S7 Cpu 1212c and 3 more 2025-04-12 N/A
Cross-site scripting (XSS) vulnerability in the integrated web server on Siemens SIMATIC S7-1200 CPU devices 2.x and 3.x allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2015-1594 1 Siemens 5 Simatic Cfc, Simatic Prosave, Simatic Step 7 and 2 more 2025-04-12 N/A
Untrusted search path vulnerability in Siemens SIMATIC ProSave before 13 SP1; SIMATIC CFC before 8.0 SP4 Upd9 and 8.1 before Upd1; SIMATIC STEP 7 before 5.5 SP1 HF2, 5.5 SP2 before HF7, 5.5 SP3, and 5.5 SP4 before HF4; SIMOTION Scout before 4.4; and STARTER before 4.4 HF3 allows local users to gain privileges via a Trojan horse application file.
CVE-2016-8561 1 Siemens 2 Simatic Cp 1543-1, Simatic Cp 1543-1 Firmware 2025-04-12 N/A
A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Users with elevated privileges to TIA-Portal and project data on the engineering station could possibly get privileged access on affected devices.
CVE-2013-0677 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-11 N/A
The web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to obtain sensitive information or cause a denial of service via a crafted project file.
CVE-2011-3389 9 Canonical, Debian, Google and 6 more 21 Ubuntu Linux, Debian Linux, Chrome and 18 more 2025-04-11 N/A
The SSL protocol, as used in certain configurations in Microsoft Windows and Microsoft Internet Explorer, Mozilla Firefox, Google Chrome, Opera, and other products, encrypts data by using CBC mode with chained initialization vectors, which allows man-in-the-middle attackers to obtain plaintext HTTP headers via a blockwise chosen-boundary attack (BCBA) on an HTTPS session, in conjunction with JavaScript code that uses (1) the HTML5 WebSocket API, (2) the Java URLConnection API, or (3) the Silverlight WebClient API, aka a "BEAST" attack.
CVE-2011-4876 1 Siemens 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more 2025-04-11 N/A
Directory traversal vulnerability in HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to execute, read, create, modify, or delete arbitrary files via a .. (dot dot) in a string.
CVE-2012-3015 1 Siemens 2 Simatic Pcs7, Simatic Step 7 2025-04-11 N/A
Untrusted search path vulnerability in Siemens SIMATIC STEP7 before 5.5 SP1, as used in SIMATIC PCS7 7.1 SP3 and earlier and other products, allows local users to gain privileges via a Trojan horse DLL in a STEP7 project folder.
CVE-2012-3028 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-11 N/A
Cross-site request forgery (CSRF) vulnerability in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to hijack the authentication of arbitrary users for requests that modify data or cause a denial of service.
CVE-2012-3030 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-11 N/A
WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, stores sensitive information under the web root with insufficient access control, which allows remote attackers to read a (1) log file or (2) configuration file via a direct request.
CVE-2012-3031 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-11 N/A
Multiple cross-site scripting (XSS) vulnerabilities in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allow remote attackers to inject arbitrary web script or HTML via a (1) GET parameter, (2) POST parameter, or (3) Referer HTTP header.
CVE-2012-3034 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-11 N/A
WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to discover a username and password via crafted parameters to unspecified methods in ActiveX controls.
CVE-2011-3321 1 Siemens 2 Simatic Wincc Flexible Runtime, Simatic Wincc Runtime 2025-04-11 N/A
Heap-based buffer overflow in the Siemens WinCC Runtime Advanced Loader, as used in SIMATIC WinCC flexible Runtime and SIMATIC WinCC (TIA Portal) Runtime Advanced, allows remote attackers to cause a denial of service (memory corruption) or possibly execute arbitrary code via a crafted packet to TCP port 2308.
CVE-2010-2772 1 Siemens 2 Simatic Pcs 7, Simatic Wincc 2025-04-11 7.8 High
Siemens Simatic WinCC and PCS 7 SCADA system uses a hard-coded password, which allows local users to access a back-end database and gain privileges, as demonstrated in the wild in July 2010 by the Stuxnet worm, a different vulnerability than CVE-2010-2568.
CVE-2013-2780 1 Siemens 18 Simatic S7-1200, Simatic S7-1200 Cpu 1211c, Simatic S7-1200 Cpu 1211c Firmware and 15 more 2025-04-11 N/A
Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to UDP port 161 (aka the SNMP port).
CVE-2013-0679 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-11 N/A
Directory traversal vulnerability in the web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote authenticated users to read arbitrary files via vectors involving a query for a pathname.
CVE-2013-0700 1 Siemens 18 Simatic S7-1200, Simatic S7-1200 Cpu 1211c, Simatic S7-1200 Cpu 1211c Firmware and 15 more 2025-04-11 N/A
Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port).
CVE-2011-4512 1 Siemens 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more 2025-04-11 N/A
CRLF injection vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary HTTP headers and conduct HTTP response splitting attacks via unspecified vectors.
CVE-2011-4877 1 Siemens 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more 2025-04-11 N/A
HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to cause a denial of service (application crash) by sending crafted data over TCP.